Revision 4 Foundation Fieldbus RMA803 Remote Indicator User's Guide Page 43
Parameter Description
WRITE_ALM This alert is generated if the write lock parameter is cleared.
ITK_VER Major revision number of the interoperability test case used in certifying this
device as interoperable. The format and range are controlled by the
Fieldbus Foundation. The current ITK version is 6.0.1.
FD_VER A parameter equal to the value of the major version of the Field Diagnostics
specification that the device is designed for.
FD_RECOMMEN_AC
T
Enumerated list of recommended actions displayed with a device alert.
FD_FAIL_PRI Designates the alarming priority of the FAIL_ALM. The valid range is 0-15.
FD_FAIL_MAP Mapped FAIL_ALM alarm conditions, and corresponds bit for bit to the
FAIL_ACTIVE. A bit on means that the corresponding alarm condition is
Mapped and it is detected. A bit off means the corresponding alarm
condition is disabled and is not detected.
FD_FAIL_MASK Mask of FAIL_ALM. It corresponds to the bit of bit to FAIL_ACTIVE. A bit on
means that the condition is masked out from alarming.
FD_FAIL_ACTIVE Enumerated list of failure conditions within a device.
FD_FAIL_ALM Alarm indicating a failure within a device which makes the device non-
operational.
FD_MAINT_PRI Designates the alarming priority of the MAINT_ALM. The valid range is 0-
15.
FD_MAINT_MAP Mapped MAINT_ALM alarm conditions and corresponds bit for bit to the
MAINT_ACTIVE. A bit on means that the corresponding alarm condition is
Mapped and is not detected. A bit off means the corresponding alarm
condition is disabled and is not detected.
FD_MAINT_MASK Mask of MAINT_ALM. It corresponds to the bit of bit to MAINT_ACTIVE. A
bit on means that the condition is masked out from alarming.
FD_MAINT_ACTIVE Enumerated list of maintenance conditions within a device.
FD_MAINT_ALM Alarm indicating the device needs maintenance soon. If the condition is
ignored, the device eventually fails.
FD_OFFSPEC_PRI Designates the alarming priority of the OFFSPEC_ALM. The valid range is
0-15.
FD_OFFSPEC_MAP Mapped OFFSPEC_ALM alarm conditions. Corresponds bit for bit to the
OFFSPEC_ACTIVE. A bit on implies that the corresponding alarm condition
is Mapped and detected. A bit off means the corresponding alarm condition
is disabled and is not detected.
FD_OFFSPEC_MAS
K
Mask of OFFSPEC_ALM. It corresponds to the bit of bit to
OFFSPEC_ACTIVE. A bit on implies that the condition is masked out from
alarming.
FD_OFFSPEC_ACTI
VE
Enumerated list of offspec conditions within a device.
FD_OFFSPEC_ALM Alarm indicating offspec alarms. These conditions do not have a direct
impact on the process or device integrity.
FD_CHECK_PRI Designates the alarming priority of the CHECK_ALM. The valid range is 0-
15.