associated with.. meaning.. ..possible action
Call point open cct
number x on loop y
Device Monitored base does not see end-of-line unit. There is
a bad connection to MCP.
Check the internal wiring, there may be a loose
connection.
Call point
operated/restored
number x loop y
Device Break glass has been broken or operated with a test
key.
Replace the break glass to restore the call point
or remove the test key, whichever is applicable.
Call point short cct
number x loop y
Device Call point contacts are short circuit. Check the call point contacts and internal
wiring.
Card found/lost at
card x
Any Card The card has been found/lost. If lost then it is locked
out.
There may be a hardware fault on card or
backplane. Investigate and rectify.
Card n recovered
/Card n backed up
NVM
(non volatile memory) on
backplane or MCB
Data recovered to a card from the NVM. A card data
has been backed up to the NVM.
-
Chamber Removed
/Replaced number x on
loop y
Device Device chamber has been removed. Replacing the chamber will cause a replaced
indication.
Charger Fault Panel
Power Supply Unit (PSU)
Charger circuit has failed. Replace the PSU.
Charger Fault
number x on loop y
EN54 System device power
supply
(Repeat, Mimic or mains
powered interface)
Charger circuit has failed at a loop device. Replace the board (having the power supply) on
the loop device.
Charger Restored Panel power supply Charger circuit is working again. -
Charger Restored
number x on loop y
EN54 System device power
supply
(Repeat, Mimic or mains
powered interface).
Charger circuit at the loop device is working again. -
Chk=4.874 NVMC 41874
Flag=0
NVM is write
protected at Card x
NVM
(non volatile memory) on
backplane or MCB
The memory is read only. Disable the write protect using the [set up]
menu.