associated with.. meaning.. ..possible action
Fire number n loop y
channel z
LPC
(loop processor card)
Pattern match is equal to a Fire or MCP operated or
conventional detection on IO line of interface operated.
-
Fire reset MCC / MCB
(main control card/board)
The Fire reset button has been pressed. -
Flash memory checksum
error
Device Speech Memory Checksum Error Replace the device
FPE Enabled /
Disabled at card x
Device All FPE Interface devices on loop x have been enabled
or disabled manually or automatically.
Manually enable or disable all FPE Interface
devices if required.
FPE w: x, y, z Device This information shows the FPE Interfaces on loop w
and are devices x, y and z.
-
Full keyboard Removed
/ Fitted number x
loop y
MCC/ MCB / DAC/ MRC The keyboard has been ‘removed’ (is not fitted). Check the cable connections to the keyboard to
bring about the ‘fitted’ message.
Group Enabled /
Disabled
MCC / MCB
(main control card/board)
A group has been automatically or manually disabled
or enabled.
If necessary, manually enable/disable the group
using the [control] menu.
High Error rate at
Card x
Network High number of communication errors. Check network wiring and connections.
Incompatible Card
Version at card x
Any Card There is a card software conflict. Fit card with compatible software.
Interface Failed at
card x
MCC / MCB
(main control card/board)
The interface timer chip has failed. Clear the fault and ignore single occurrence.
Replace the card on multiple failures.
Interface input -
fault / restored
number x on
loop y channel z
Device IO line fault. Check the wiring and restore the input for
normal operation.
Interface Input Fire
number x on loop y
channel z
Device Interface IO line triggered a fire event. Check the wiring and restore the input for
normal operation.