Message
associated with.. meaning.. ..possible action
Master alarm
enabled/disabled
MCC / MCB
(main control card/board)
The master alarm has been enabled or disabled
automatically or manually.
If necessary, manually enable or disable the
master alarm using the [control] menu.
Master alarm restored Power supply Master alarm fault cleared.
The ADC value should be 74.
Master polling/not
polling at card x
MCC / MCB PC or SRI (service request interface) is not
handshaking with the control panel
Check the wiring
Master Sector
Actioned
MCC / MCB
(main control card/board)
Master sector has been switched ON/OFF. -
Master Sector
Enabled/Disabled
MCC / MCB
(main control card/board)
Master sector has been enabled or disabled manually or
automatically.
If necessary manually enable or disable the
master sector.
Memory corrupt
number x loop y
Device FLASH checksum failure Replace the device
Message discarded Network Card
LPC
(loop processor card)
Message received that couldn’t be routed or
understood.
Check the location displayed, try resetting card.
Neighbour ACK Failed
at card n
- Repeated address Check domain addresses are unique
Neighbour ACK Invalid
at card n
TBA TBA TBA
Network initialised
at card x
Network Card Successful network map with polled panels. -
Network Insecure /
Secure at card x
Network Card There are 3 missing replies in a row on End-2 of the
controller.
Check the wiring.
Check the error rate.
Network starting at
card x
Network Card Communication starting with other connected panels. -
Network wiring fault
at card x
Network Card Wiring is presumed to be OC between
panel n and panel n.
Check the wiring.
New address n at
card x
MCC / MCB
Network Card
The new address set has been read. -
Commissioning instructions
130 4188-856_issue 7_07/15_Generic Vigilon (Compact + VA) Comms.
Appendix B - Message Action List