Message
associated with.. meaning.. ..possible action
New domain address n
at card x
Network Card The new address set been read at the particular card. -
NMI’s missed at
card x
LPC
(loop processor card)
Software error. Software errors will activate a system reset.
Ignore single occurrence. Record the event in
the log book.
No periodic
interrupts at card x
Any Card Problem with software, the watchdog will operate the
MCC / MCB (main control card/board).
Software error will activate a system reset.
Ignore single occurrence. Record event in the
log book.
No response number x
loop y
LPC
(loop processor card)
There is no communication with repeat or mimic panel
software.
Power-up the repeat or mimic panel.
No room on NVM card NVM
(non volatile memory) on
backplane or MCB
User attempts to backup or save to an NVM that does
not have enough free space
If there is no memory left then the card 14
located on the Backplane or on
MCB (Card 0) needs to be initialised
Node double allocated
at card x
Network Card Two network cards have same address. Keep address unique.
Node found at card x Network Card Another panel on the network acknowledged. -
Node lost/restored at
card x
Network Card There have been 15 missing replies from another panel. Check the wiring or check and reset the panel
Network card to restore.
Not enough RAM at
card x
Any Card Not enough memory. Reset the card and ignore single occurrence. If
necessary replace the card or add RAM, where
applicable.
Nothing found at
card x
LPC
(loop processor card)
No devices found on End 1 or End 2. Check wiring of loop circuit.
NVM initialised NVM
(non volatile memory)on
backplane or MCB
Memory available verified. -
NVM is not write
protected
NVM
(non volatile memory)on
backplane or MCB
Read and write is possible to the memory card. Enable protect if required using the [set up]
menu.
4188-856_issue 7_07/15_Generic Vigilon (Compact + VA) Comms. 131
Vigilon 4/6 loops & Compact (VA) panels & network nodes
Appendix B - Message Action List

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Honeywell Vigilon 4 loop and is the answer not in the manual?

Honeywell Vigilon 4 loop Specifications

General IconGeneral
BrandHoneywell
ModelVigilon 4 loop
CategoryControl Panel
LanguageEnglish

Related product manuals