EasyManua.ls Logo

Honeywell XNX - Page 119

Honeywell XNX
200 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
XNX Universal Transmitter
Section 5 - Warnings/Faults
117
Fault Description
Appli-
cable
Sensors
Latching / Non-
Latching
Frequency of
Diagnostic
Event History Data Action For Resolution
F149
Internal4-20mA
monitoringcircuit
communication
failure
All Non-latching 3�366seconds 0 ContactHoneywellAnalytics’ServiceDepartment�
F150
mAOutputMonitor
Communications
WatchdogError
All Non-latching 138us
Communicationerror
count
ContactHoneywellAnalytics’ServiceDepartment�
F151
SensorModule
TypeChanged
ECC Non-latching 2seconds
Moduletype:0=None,
1=ECC,2=mV,
3=Excel,4=Optima,
5=GenericmA
ForECC:PerformAcceptNewSensorfunction,ifproblempersists
contactHoneywellAnalytics’ServiceDepartment�Forothers,contact
HoneywellAnalytics’ServiceDepartment�
F152
OptionModule
CongurationError
All Latching
Onlyatpowerup
orevery125ms
whennooption
boarddetected
OptionmoduleID:
0=None,1=Founda-
tionFieldbus,2=Mod-
bus,3=Relay
Conrmoptionproperlyinstalled,recongureunit�
F153
Signal/Datamis-
matcherroronIR
personality
Optima,
Excel
Non-latching 2seconds Digitalsensorreading
CheckwiringtoOptima/Excel�Inparticular,checkthewhitewirebe-
tweenXnXandOptima/Excel�Note:powermustbecycledtoresetF153
aftercorrectingthecause�
F154
mAInputDiagnos-
ticFailure
Optima,
Excel
Latching
5minutesafter
powerupand
thenevery8
hours
InputmA ContactHoneywellAnalytics’ServiceDepartment�
F155
GenericmASensor
TypeError
Generic
mA
Non-latching 2seconds InputmA
IndicatesthatmAinputfromsensorislessthan3mA�Checkwiring
betweenXNXandsensor�AlsochecktheswitchesS3andS4areset
correctly�Iftheswitchsettingsneedtobechange,powerdowntheXNX
beforechangingtheswitchsettings�Ifwiringandswitchesareokay,
replacesensor
F156
mVCurrentControl
Failure
mV Non-latching Mainloopx16
constantcurrentA/D
inputmV
CheckthatcorrectmVsensortypeisselected�Checkwiringbetween
XNXandsensor�Ifsensortypeandwiringareokay,replacesensor
F157 SensorDriftFault ECC,mV Non-latching 2seconds Currentbaseline Performzerocalibration�Ifproblempersists,replacesensor
F158
Sensor/Personal-
ityPartNumber
mismatch
All Non-latching
"ECC&mV:main
loopx2;
Optima&Excel:2
seconds"
Entirepersonality
part#
CheckthatinstalledoptionmatchestheoptionindicatedintheXNXpart
number,checkwiringtoOptima/Excel�

Table of Contents

Other manuals for Honeywell XNX

Related product manuals