Section 6 - Specications
140
Gas type Part Number Gas Type Applied Concentration Unit Reading Unit
H
2
(HighRange) XNXXSG2SS
Ammonia 100 ppm 0 ppmH
2
Arsine 0.2 ppm 0 ppmH
2
CarbonDioxide 1000 ppm 0 ppmH
2
CarbonMonoxide 100 ppm 150 ppmH
2
Chlorine 1 ppm 0 ppmH
2
Ethylene 500 ppm yes;n/d ppmH
2
HydrogenCyanide 20 ppm 0 ppmH
2
HydrogenSulfide 20 ppm 4 ppmH
2
Iso-Propanol 1100 ppm yes;n/d ppmH
2
Methane 1 % 0 ppmH
2
NitrogenDioxide 10 ppm -40 ppmH
2
Ozone 0.25 ppm 0 ppmH
2
SulfurDioxide 5 ppm 0 ppmH
2
HF XNXXSF1SS
CarbonMonoxide 2000 ppm 0 ppmHF
Hydrogen 20000 ppm 0 ppmHF
Chlorine 5 ppm 3.4 ppmHF
NitrogenDioxide 5 ppm 0.65 ppmHF
Iso-Propanol 500 ppm 0 ppmHF
Methanol 500 ppm 0 ppmHF
HydrogenFluoride 5 ppm 7 ppmHF
HydrogenSulfide 25 ppm -3.6 ppmHF
SulfurDioxide 50 ppm 28.3 ppmHF
Arsine 1 ppm 0 ppmHF
Phosphine 1 ppm -0.14 ppmHF
Diborane 1 ppm -1.3 ppmHF

Table of Contents

Other manuals for Honeywell XNX

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Honeywell XNX and is the answer not in the manual?

Honeywell XNX Specifications

General IconGeneral
Ingress ProtectionIP66/67
Product TypeUniversal Transmitter
Enclosure RatingIP66/67
DisplayLCD
Communication ProtocolsHART, Modbus, Foundation Fieldbus
Power Supply24 VDC nominal, 18-32 VDC
Operating Temperature-40°C to +65°C (-40°F to +149°F)
MaterialAluminum or Stainless Steel
Gas TypesToxic, Oxygen, and Combustible gases
Output4-20 mA
Relays3 programmable relays
ApprovalsATEX, IECEx, UL, CSA
Sensor CompatibilityElectrochemical, catalytic, infrared, and other sensor types