EasyManua.ls Logo

Honeywell XNX - 8.1.6 MPD Flammable Sensor; 8.1.7 Cross Calibration procedure for MPD-CB1

Honeywell XNX
200 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
XNX Universal Transmitter
Section 2 - Installation and Operation
50
theSearchlineExcelTechnicalHandbook(2104M0506)or
SearchpointOptimaPlusOperatingInstructions(2104M0508)
forspecicsonremoteinstallationsorcontactyourHoneywell
Analyticsrepresentativeformoreinformation�
Searchpoint Optima Plus or Searchline Excel Wiring Recommendations
WhenwiringtheXNXtransmitterandtheSearchpointOptima
PlusorSearchlineExcelforremoteapplications,thegeneral
recommendationsoftheANSI/TIA/EIA-485-Astandardmustbe
adheredtowiththefollowingadditions:
1�WhenmountingtheSearchlineExcelorSearchpoint
OptimaPlus,runwiringconnectionsbetweeneachExcel
orOptimaandthetransmitterinadedicatedseparate
conduit�
2�Use18AWGtwistedshieldedcablefortheRS485
connectionbetweenExcelorOptimaandtheXNX�Make
surethattheshieldofthecableisgroundedtoearthand
XNXgroundononeendONLY
3�Avoidrunningwiringnearmaincablesorotherhigh
voltageequipment�
4�Do
not
apply120ohmterminatingresistors�These
resistorsarenotrequiredduetolowdatarates�
5�HoneywellAnalyticsrecommendsthatExcelorOptima
sensorsandtheXNXtransmitterbewiredtobuilding
ground�Thesystemshouldbegroundedatonepointonly
INSTALLATION TIP:
AlwaysperformasoftresetafterconnectingtheSearchpoint
OptimaandXNXtransmitterforthersttime�Thesoftresetis
performedbyaccessingthetransmitter’sCalibrationMenu�
HART
20 mA
Operation
LOCAL
J1
S1
+V 1-1
Searchline
Searchpoint
4-20mA
HART
18-32 VDC
13.2W max.
1-2
-V 1-3
1-4
+mA 1-5
-mA 1-6
1-7
- Ir
+ Ir
1-8
Sig 1-9
S1
Source
Sink
Isolated
S2
S2
Ir TB-1
TB-2 Ir Data
S3
Source
Sink
S4
IR Sens (silver)
IR +ve (red)
IR -ve (black)
RS485+ (yellow)
RS485- (blue)
IR Sens
IR +ve
IR -ve
RS485+
RS485-
Twisted Shielded Pair
18 AWG
Single Ground Point
RS485 Cable Shield
Ground ONE END ONLY
Power Supply
+ve
-ve
Junction Box
Searchline Excel
Searchpoint Optima Plus
Pair 1: Unit Ground and IR Sense
(Cable Shield Grounded ONE END ONLY)
Pair 2: RS485+ and RS485-
(Cable Shield Grounded ONE END ONLY)
Pair 3: IR +ve and IR -ve
(Cable Shield Grounded ONE END ONLY)
Unit Gnd (green)
Figure 55. XNX IR Remote
Wiring

Table of Contents

Other manuals for Honeywell XNX

Related product manuals