5 Commissioning
Linear actuators MC55
Operating Manual Version 3.3 - November 2014 21
5.5 Setting the limit position for MC55Y
Use Jumper JP2 to select a limit position for the linear actuator.
• JP2 ON: Limit position with extended spindle nut
• JP2 OFF: Limit position with retracted spindle nut
The limit position is approached in the following situations:
• Due to wire break detection by the Y signal (2 … 10 V DC or 4 … 20 mA
only),
• Due to a binary signal (When electric circuit between terminal B1 and B2 is
interrupted),
5.6 Commissioning
1 Check whether all fitting and assembly work has been competently finished.
4 Assembly on page 11
2 Ensure that the electrical actuation of the linear actuator can take place safely
without putting people or devices at risk.
3 Ensure that the linear actuator is attached correctly and that the cover of the
linear actuator is closed.
4.4 Assembling/disassembling the cover on page 13
4 Ensure that the linear actuator is set to automatic mode.
6.1 Changing between manual and automatic mode on page 22
5 Ensure that the operating parameters are set correctly.
5.1 Operating parameters and jumper settings on page 19
6 Apply supply voltage. The linear actuator will now move to the reference point.
The linear actuator is ready for operation.