EasyManuals Logo

hpmont MONT20 User Manual

hpmont MONT20
79 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #11 background imageLoading...
Page #11 background image
Chapter 2 Product Information
4 MONT20 User Manual V1.6
Input and Output
Power supply +24V, Max. output current is 200mA
Digital input DI1 - DI5, OD, CD
Relay output
DOA, DCA, PA , PB, PC
Contact rating: 125VAC/0.5A or 24VDC/1A
Communication CAN+, CAN-
Keypad
Optional LCD keypad 8 keys, 5 digit 8 segment nixie tube display, 5 unit indicators, 5 status indicators
Optional LED keypad 8 keys, 5 LED nixie tube, 5 unit indicators, 5 status indicators
LCD/LED display Set function parameter, check status parameter, check fault code, etc.
Environment
Running temperature
-10 - +40
, Max. 50
, air temperature fluctuation is less than 0.5
/min
The derating value of output current shall be 2% for each degree centigrade above
40
. Max. allowed temperature is 50
Storage temperature -40 - +70
Applicable place
Indoor, preventing from direct sunlight, no dust, corrosive, flammable gases, oil mist,
water vaper, dripping or salt etc.
Altitude Less than 1000 meters, otherwise it should be derating use
Humidity Less than 95%RH, non-condensing
Vibration resistance It is 3.5m/s
2
in 2 - 9Hz, and 10m/s
2
in 9 - 200Hz (IEC 60721-3-3)
Protection class IP20
Pollution level 2 (dry, non conducting dust pollution)
Accessories
About keypad
LED keypad [HD-LED]
1m extension cable to keypad [HD-CAB-1M]

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the hpmont MONT20 and is the answer not in the manual?

hpmont MONT20 Specifications

General IconGeneral
Brandhpmont
ModelMONT20
CategoryController
LanguageEnglish

Related product manuals