Item Specications
Frequency 50/60 Hz
Input current Maximum current: 30 A
Input capacity 6 kVA
PV input Open-circuit voltage 85–435 V DC
MPPT voltage 90–420 V DC
Number of MPPT
circuits
1
MPPT capacity 5.5 kWp
PV branch 2
Maximum input
current
15 A
Maximum short-
circuit current
18 A
Maximum number
of PV optimizers
connected
8 PCS
AC
output
[1]
Output voltage 200/208/220/230/240 V AC, default value: 220 V AC
Output frequency 50/60 Hz, default value: 50 Hz
Output power Maximum: 6 kVA/5 kW
Output current Maximum current: 30 A
Power factor 0.83
Battery module capacity
[2]
5 kWh/battery module. A maximum of six battery modules
can be connected to a power module.
Bypass input frequency 6 kW
Overload capability ● 102% ≤ Load ≤ 125%: 30s
● 125% < Load ≤ 150%: 10s
● > 150%: short circuit, 0.3s
Surge
protection
AC input Dierential mode: 3 kA (8/20 μs), common mode: 5 kA (8/20
μs), criterion C
PV input Common mode: 10 kA, 8/20 μs, criterion C
Note [1]: The output voltage and frequency must be the same as those of the local power grid.
Note [2]: Test conditions: 100% DOD, 0.2C rate charge & discharge at 25°C, at the beginning of
life.
iSitePower-M V100R002C00 User Manual
(MAP05A1, MAB05B1)
iSitePower-M V100R002C00 User Manual
(MAP05A1, MAB05B1) A Technical Specications
Issue 01 (2022-07-15) Copyright © Huawei Technologies Co., Ltd. 181