Table A-3 EMC specications
Item Specications
Electromagnetic
interference
(EMI)
Conducted emission
(CE)
IEC 62920\CISPR11\EN 62040-2
AC port: Class B; DC port: Class B; signal port: Class B;
FE port: Class B
Radiated emission
(RE)
IEC 62920\CISPR11\EN 62040-2
Class B
Harmonic current IEC 61000-3-12
AC power port: The current of each phase is greater
than 16 A.
Voltage uctuation
and icker
IEC 61000-3-12
AC power port: Pst ≤ 1.0, P1t ≤ 0.65, dc ≤ 3%, dmax ≤
4%. The time when the value of d(t) exceeds 3% is
less than or equal to 200 ms.
Electromagnetic
susceptibility
(EMS)
Electrostatic
discharge (ESD)
IEC 61000-4-2
Enclosure port: 6 kV (level B) contact discharge, 8 kV
(level B) air discharge
Electrical fast
transient (EFT)
IEC 61000-4-4
AC power port: 2 kV, DC power port: 2 kV, signal port:
1 kV (criterion B)
Radiated
susceptibility (RS)
IEC 61000-4-3
Enclosure port: The test frequency range is 80 MHz to
6 GHz, 80% AM (1 kHz) modulation is used, and the
test level is 10 V/m.
Conducted
susceptibility (CS)
IEC 61000-4-6
0.15–80 MHz: 10 V, 80% AM (1 kHz) modulation
iSitePower-M V100R002C00 User Manual
(MAP05A1, MAB05B1)
iSitePower-M V100R002C00 User Manual
(MAP05A1, MAB05B1) A Technical Specications
Issue 01 (2022-07-15) Copyright © Huawei Technologies Co., Ltd. 182