Parallel
Power
Module
CAN
Address
Pin 1
(M/S)
Pin 2 (A) Pin 3 (B) Pin 4 (C) Remarks
3 OFF OFF ON OFF Slave
address
COM and Dry Contacts
Figure 3-4 Wiring terminals
Table 3-2 Terminals on the panel
Pin
Signal Description Function
1 RS485A RS485 signal Reserved ports
2 RS485B
3 NC Dry contact
output NC
terminal
Connect to a
genset and
control genset
startup and
shutdown
signals
[1]
.
可接EPO急停开关,
实现设备远程关
断。
4 COM Dry contact
output common
terminal
5 NO Dry contact
output NO
terminal
6 DIN1+ Dry contact input
DIN 1
These ports are
reserved and can
connect to an ATS. In
the grid + genset
scenario, the DIN dry
contacts are used to
detect grid signals.
7 DIN1-
9 DIN2+ Dry contact input
DIN 2
10 DIN2-
8 GND
-
-
iSitePower-M V100R002C00 User Manual
(MAP05A1, MAB05B1)
iSitePower-M V100R002C00 User Manual
(MAP05A1, MAB05B1) 3 Components
Issue 01 (2022-07-15) Copyright © Huawei Technologies Co., Ltd. 29

Table of Contents