NetCol5000-A 42 kW Air Cooled In-row Precision Air
Conditioner
User Manual
5 Operation and Maintenance
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
switch is blocked or
disconnected.
5. The cables to the
differential press switch
are loose or damaged.
5. Check the cables to the
differential press switch.
Air filter
exceed
runtime
The accumulated runtime of
the air filters exceeds the
alarm set point.
Maintain or replace the air
filters. Tap Maint >
Performance Maint to clear
the accumulated runtime.
The supply power is cut off.
Check the power supply
cables.
The alarm
is
generated,
and the
system
shuts
down.
1. The power supply voltage
is too high.
2. The SPD three-phase test
board is faulty.
1. Check the power supply
voltage, Ensure that the
voltage is within the
operating range.
2. Replace the SPD
three-phase test board.
The alarm
is
generated,
and the
system
shuts
down.
1. The power supply voltage
is too high.
2. The SPD three-phase test
board is faulty.
1. Check the power supply
voltage, Ensure that the
voltage is within the
operating range.
2. Replace the SPD
three-phase test board.
The alarm
is
generated,
and the
system
shuts
down.
1. The power supply voltage
is too high.
2. The SPD three-phase test
board is faulty.
1. Check the power supply
voltage, Ensure that the
voltage is within the
operating range.
2. Replace the SPD
three-phase test board.
The alarm
is
generated,
and the
system
shuts
down.
1. The power supply voltage
is too low.
2. The SPD three-phase test
board cable is not
properly connected.
3. The SPD three-phase test
board is faulty.
1. Check the power supply
voltage.
2. Check the cable
connection to the SPD
three-phase test board.
3. Replace the SPD
three-phase test board.
The alarm
is
generated,
and the
system
shuts
down.
1. The power supply voltage
is too low.
2. The SPD three-phase test
board cable is not
properly connected.
3. The SPD three-phase test
board is faulty.
1. Check the power supply
voltage.
2. Check the cable
connection to the SPD
three-phase test board.
3. Replace the SPD
three-phase test board.