NetCol5000-A 42 kW Air Cooled In-row Precision Air
Conditioner
User Manual
5 Operation and Maintenance
Issue 01 (2017-07-27)
216
Figure 5-66 Installing a relay
Step 5 Power on the device, and ensure that the air conditioner works properly without alarms.
Step 6 Install the air filter and close the rear door.
----End
5.4.20 Replacing the Fuse
Prerequisites
The fuse, as shown in A Electric Control Box Layout, needs to be replaced.
A spare fuse of the same model is available and functional.
Tool: flat-head screwdriver
Procedure
Step 1 On the controller home screen, tap Shutdown, and turn off the air conditioner switch in the
PDC.
Exercise caution because the device is still energized after it is shut down on the controller
home screen.