NetCol5000-A 42 kW Air Cooled In-row Precision Air
Conditioner
User Manual
4 Commissioning
Issue 01 (2017-07-27)
103
Parameter
Setting
Setting Method
a client, can connect to a remote server and establish
communication.
If you set Link mode to Server and client, the air
conditioner, as a server, supports two client
connection and establishes communication. In
addition, the air conditioner, as a client, can connect to
a remote server and establish communication.
Client
encrypt
Enable,
Disable
The default value is Enable. This parameter is
configurable when Link mode is set to Client.
Server
encrypt
Enable,
Disable
The default value is Disable. This parameter is
configurable when Link mode is set to Server.
Network IP
N/A
Enter the actual IP address of the EMS. IP addresses of
the display panel, EMS client, and EMS server must be
unique. This parameter is configurable when Link mode
is set to Client.
Network
port
N/A
It is recommended that you retain the default value
16100. If you need to change the value, enter a value as
required. This parameter is configurable when Link
mode is set to Client.
----End
4.5.7 Setting Communications Parameters (SNMP Parameters)
Context
To set communications parameters, log in as the admin user.
This section is suitable only for SNMP. Skip this section if you use Modbus.
Record the values entered in this section. They will be used when you access a precision
air conditioner to an EMS (element management system).
One precision air conditioner supports concurrent access of up to 10 EMSs through
SNMP.
Procedure
Step 1 On the home screen, choose Settings > Comm Settings > SNMP Settings. Figure 4-15 is
displayed.