NetCol5000-A 42 kW Air Cooled In-row Precision Air
Conditioner
User Manual
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
Saturation
Pressure-S
urface
Pressure
(MPa)
Saturation
Pressure-S
urface
Pressure
(MPa)
Saturation
Pressure-S
urface
Pressure
(MPa)
3.2.2.2 (Optional) Pipe Assembly
Liquid pipe:
− L ≤ 60 m: R410A copper pipe; outer diameter of 5/8 inch (15.88 mm); wall
thickness of 1.0 mm; operating pressure > 4.5 MPa
− 60 m < L ≤ 100 m: R410A copper pipe; outer diameter of 3/4 inch (19.05 mm); wall
thickness of 1.2 mm; operating pressure > 4.5 MPa
Gas pipe requirements: R410A copper pipe; outer diameter of 7/8 inch; thickness of 1.2
mm; operating pressure ≥ 4.5 MPa
Thermal insulation foam: thickness ≥ 9.2 mm