NetCol5000-A 42 kW Air Cooled In-row Precision Air
Conditioner
User Manual
3 Installation Guide
Issue 01 (2017-07-27)
71
Place the sheet metal of the water sensor upwards and its detection board downwards on the
ground.
Figure 3-43 Connecting a cable to the water sensor
----End
3.11.2.3 (Optional) Installing the Differential Pressure Sensor
Context
The differential pressure sensors are optional components and installed with sheet metal
fasteners before delivery. Secure the fasteners, install the pressure inlet tube, and connect
cables onsite.
Procedure
Step 1 Secure the differential pressure sensor and the fasteners using M5 tapping screws, as shown in
step 1 in Figure 3-44.