NetCol5000-A 42 kW Air Cooled In-row Precision Air
Conditioner
User Manual
5 Operation and Maintenance
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
dirty/blocked & heat ex
effect poor.
5. The drive module is
faulty.
1. The cables to phase U of
the comp driver are loose
or damaged.
2. The comp driver is faulty.
1. Check the cables to the
comp driver.
2. Maintain or replace the
comp driver.
1. The cables to phase V of
the comp driver are loose
or damaged.
2. The comp driver is faulty.
1. Check the cables to the
comp driver.
2. Maintain or replace the
comp driver.
1. The cables to phase W of
the comp driver are loose
or damaged.
2. The comp driver is faulty.
1. Check the cables to the
comp driver.
2. Maintain or replace the
comp driver.
The alarm
is
generated,
and the
compresso
r shuts
down.
1. The comp is in lack of
oil.
2. The condenser is blocked.
3. Outdoor fans run
abnormally.
4. The refrigerant is
overfilled.
5. The comp is faulty.
1. Fill oil to the comp.
2. Clean the condenser fins.
3. Maintain or replace
outdoor fans.
4. Decrease certain amount
of refrigerant.
5. Maintain or replace the
comp.
Indoor fan
1, 2, 3, 4,
5, 6, 7, 8,
9, or 10
fault
The alarm
is
generated.
Can not
start the
compresso
r,
humidifier
, and
electric
heater.
1. The power supply to the
indoor fan is abnormal.
2. The cables to the indoor
fan are loose or damaged.
3. The indoor fan is faulty.
1. Check the power supply
to the indoor fan.
2. Check the cables to the
indoor fan.
3. Maintain or replace the
indoor fan.
The alarm
is
generated,
and the
system
shuts
down.
1. The cables to the high
float are loose or
damaged.
2. The high float is faulty or
stuck.
3. The condensate pump is
faulty, or the drainage
capacity decreases.
4. The pipeline or the
internal drainpipe is
blocked or frozen.
1. Check the cables to the
high float.
2. Maintain or replace the
high float or clear the
obstacles.
3. Reference to the solutions
for the a041 cond pump
fault alarm.
4. Clear the internal
drainpipe.
1. The cables to the high