NetCol5000-A 42 kW Air Cooled In-row Precision Air
Conditioner
User Manual
5 Operation and Maintenance
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
Indoor fan
1, 2, 3, 4,
5, 6, 7, 8,
9 or 10
overspeed
1. The cables to the indoor
fan are loose or damaged.
2. The indoor fan is faulty.
1. Check the cables to the
indoor fan.
2. Maintain or replace the
indoor fan.
The indoor fan is faulty.
Maintain or replace the
indoor fan.
Cold-aisle
1, 2, 3, 4,
5 temp
invalid
1. The cables to the T/H
sensor are loose or
damaged.
2. The T/H sensor is faulty.
1. Remove dirt or water
from the T/H sensor.
2. Maintain or replace the
T/H sensor.
Cold-aisle
1, 2, 3, 4,
5 humid
invalid
1. The cables to the T/H
sensor are loose or
damaged.
2. The T/H sensor is faulty.
1. Remove dirt or water
from the T/H sensor.
2. Maintain or replace the
T/H sensor.
Cold aisle
1, 2, 3, 4,
5 T/H brd
comm
failed
1. The cables to the T/H
sensor are loose or
damaged.
2. The DIP switch of the
T/H sensor is set
incorrectly.
3. The T/H sensor is faulty.
4. The communication port
of the control board is
faulty.
1. Check the cables to the
T/H sensor.
2. Set the DIP switch of the
T/H sensor correctly.
3. Maintain or replace the
T/H sensor.
4. Maintain or replace the
control board.
Hot-aisle
1, 2, 3, 4,
5 temp
invalid
1. The cables to the T/H
sensor are loose or
damaged.
2. The T/H sensor is faulty.
1. Remove dirt or water
from the T/H sensor.
2. Maintain or replace the
T/H sensor.
Hot-aisle
1, 2, 3, 4,
5 humid
invalid
1. The cables to the T/H
sensor are loose or
damaged.
2. The T/H sensor is faulty.
1. Remove dirt or water
from the T/H sensor.
2. Maintain or replace the
T/H sensor.
Hot-aisle
1, 2, 3, 4,
5 T/H brd
comm
failed
1. The cables to the T/H
sensor are loose or
damaged.
2. The DIP switch of the
T/H sensor is set
incorrectly.
3. The T/H sensor is faulty.
4. The communication port
of the control board is
faulty.
1. Check the cables to the
T/H sensor.
2. Set the DIP switch of the
T/H sensor correctly.
3. Maintain or replace the
T/H sensor.
4. Maintain or replace the
control board.
1. The monitoring host
(ECC) is faulty.
1. Check that the
monitoring host (ECC)