2. Verify that the suction
temperature sensor works
properly.
Outdoor
fan
communic
ation
failure
1. The indoor and outdoor
communications cable is
not properly connected.
2. The outdoor fan driver is
faulty.
3. The outdoor unit is not
powered on.
4. The communication port
of the control board is
faulty.
1. Check the indoor and
outdoor communications
cable.
2. Maintain or replace the
outdoor fan driver.
3. Power on the outdoor
unit.
4. Maintain or replace the
control board.
The outdoor fan running
time exceeds the upper limit.
Replace the outdoor fan, and
clear the accumulated
running time.
Outdoor
fan Dr
hardware
protect
1. The driver output cable is
short-circuited or
grounded.
2. The fan is faulty.
3. The power grid voltage
exceeds the upper
threshold.
1. Replace the driver output
cable.
2. Replace the fan.
3. Power off and verify that
the input power supply
voltage meets the
specifications.
Clean the fan and remove
obstacles to ensure that the
fan works properly.
Outdoor
fan Dr OP
open
phase
1. A driver output cable
connector or fan input
cable connector is loose.
2. A cable is not properly
connected.
1. Secure the driver output
cable.
2. Replace the driver output
cable.
R/W fail
of outdoor
fan Dr
Power off the driver and
power it on 10s later.
Replace it if the alarm
persists.
Outdoor
fan Dr
12V
undervolt
The auxiliary power supply
is faulty.
Outdoor
fan grid
overvolt
The power grid voltage
exceeds the upper threshold.
Power off the driver and
verify that the supply voltage
meets specifications.
The power grid has an open
phase, or its voltage is below
Secure the power grid input
cable, power off the driver,
and verify that the supply