NetCol5000-A 42 kW Air Cooled In-row Precision Air
Conditioner
User Manual
5 Operation and Maintenance
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
Auxiliary
power
24V
overvoltag
e
The auxiliary power supply
is faulty.
Replace the auxiliary power
supply module.
Auxiliary
power
24V
undervolta
ge
The auxiliary power supply
is faulty.
Replace the auxiliary power
supply module.
The alarm
is
generated,
and the
system
shuts
down.
1. The power grid is
unstable.
2. The phase A cable is
faulty.
1. Check the power grid.
2. Check the phase A cable
is faulty.
The alarm
is
generated,
and the
system
shuts
down.
1. The power grid is
unstable.
2. The phase B cable is
faulty.
1. Check the power grid.
2. Check the phase B cable
is faulty.
The alarm
is
generated,
and the
system
shuts
down.
1. The power grid is
unstable.
2. The phase C cable is
faulty.
1. Check the power grid.
2. Check the phase C cable
is faulty.
SPD
3-phase
test board
comm
fault
1. The communications
cable is not properly
connected.
2. The SPD three-phase test
board is faulty.
3. The communication port
of the control board is
faulty.
1. Check the
communications cable.
2. Replace the SPD
three-phase test board.
3. Maintain or replace the
control board.
The SPD three-phase test
board is faulty.
Replace the SPD three-phase
test board.
L1/L2
linkage
humidity
not met
1. The cabinet T/H sensor is
faulty.
2. The cables to the cabinet
T/H sensor are loose or
damaged.
1. Maintain or replace the
cabinet T/H sensor.
2. Maintain or replace the
cables to the temperature
sensor, rack environment