NetCol5000-A 42 kW Air Cooled In-row Precision Air
Conditioner
User Manual
5 Operation and Maintenance
Issue 01 (2017-07-27)
166
Figure 5-11 Angle valve
(1) Angle valve nut
(2) Adjustable nut
(3) Pipe nut
Procedure
Step 1 On the controller home screen, tap Shutdown, and turn off the air conditioner switch in the
PDC.
Exercise caution because the device is still energized after it is shut down on the controller
home screen.
Step 2 Open the rear door and remove the air filter.
Step 3 Reclaim the refrigerant.
Step 4 Remove the electric heating belt.
Step 5 Remove the cover of the connection box and disconnect the compressor power cables.