NetCol5000-A 42 kW Air Cooled In-row Precision Air
Conditioner
User Manual
C Parameter Description
Issue 01 (2017-07-27)
255
Menu
Parameter
Description
Default Value
Time zone
Specifies the time zone displayed on the
ACC.
Consistent with the
current interface
time zone
Maint >
Performance
Maint
Compressor total
runtime, Indoor
fan total runtime,
Outdoor fan total
runtime, Elec
heater total
runtime,
Humidifier pump
running time,
Humidifier
running time,
pump total
runtime, Air filter
total runtime, Total
EEV total runtime
Total runtime for each component.
0h
Maint > Sensor
Adjust
Supply-air temp
adj value,
Return-air temp
adj value,
Return-air humid
adj value, Comp
discharge temp adj
value, Comp
discharge pres adj
value, Comp
suction temp adj
value, Comp
suction pres adj
value, Comp liq
pipe temp adj
value, Side
calibrated pressure
difference value
Specifies the adjustment value of each sensor
when the detected temperature or humidity
varies from the practical value. For example,
if the detected return air temperature is 1°C
lower than the value detected by other
devices, set the calibration value to 1°C.
0.0°C, 0.0% RH, 0
Pa, or 0.00 MPa