Parameter
Index
Meaning Default Setting
83-127 Reserved parameters 65535
A.4.3 Setting the Default Parameters of the EMU
Table A-5 and Table A-6 provide the parameter settings of the EMU on the UA5000.
Table A-5 Default parameter settings of the H303ESC and H304ESC
Parameter Default Setting
Sub-node 15
Analog parameters ESC analog parameter IDs
l 0: allocated to the temperature sensor by default (read-only).
l 1-4: allocated to the voltage sensor by default.
1 indicates -48 V input of channel 0.
2 indicates -48 V input of channel 1.
3 indicates -48 V input of channel 2.
4 indicates -48 V input of channel 3.
l 5-8 indicate user-defined analog parameters to be allocated to other
extended analog sensors, such as humidity sensor.
Upper and lower alarm thresholds
l Temperature: 5°C to 55°C
l Humidity: 0% RH to 80% RH
Digital parameters ESC digital parameter IDs
l Allocated by default (read-only)
0: MDF
1: door status sensor 0
9: water
10-13: lightning arresters 0-3
14-15: switches 11 and 12
16-17: switches 21 and 22
18-19: switches 31 and 32
20-21: switches 41 and 42
22: external sensor power
l User-defined IDs
2-8: allocated to other extended digital sensors.
UA5000 Universal Access Unit Product
Commissioning Guide-PVM CLI A Additional Information
Issue 04 (2012-06-25) Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
125