18: P
ULSE
O
UTPUT
I
NSTRUCTIONS
â–  Settings tab
6. Steady pulse frequency
This setting specifies the steady pulse frequency after the pulse frequency is increased. Set between 15 and 100 kHz in 1 Hz
increments. The output frequency error is within ±5%.
For JOG3 and JOG4 with the All-in-One CPU module, set between 15 and 5 kHz in 1 Hz increments.
7. Initial pulse frequency
Specifies the frequency when pulse output starts. Set between 15 and 100 kHz in 1 Hz increments. The output frequency error
is within ±5%.
For JOG3 and JOG4 with the All-in-One CPU module, set between 15 and 5 kHz in 1 Hz increments.
8. Acceleration time
Specifies the time to increase the pulse frequency. Set the value in the range of 10 to 10,000 ms in increments of 1 ms. The first
digit of the setting is handled as zero. For example, if 144 is entered, the set value is handled as 140 ms.
9. Deceleration time
This setting specifies the time to decrease the pulse frequency. Set the value in the range of 10 to 10,000 ms in increments of
1 ms. The first digit of the setting is handled as zero. For example, if 144 is entered, the set value is handled as 140 ms.
10. Reversible control enable
This setting enables or disables reversible control and selects the reversible control method from the following reversible control
modes. There are two modes for the pulse output mode: single-pulse output mode and dual-pulse output mode. They can be
combined with reversible control as follows. (This is an example when JOG1 is used with the All-in-One CPU module.)
The used outputs differ by the instruction used, the combination of the pulse output mode and reversible control, and the model
used.
Reversible Control Enable Operation Pattern
Reversible control disabled
Select this option when using pulse output in a single
direction. Pulse A and pulse B can be used independently.
Reversible control Single-pulse
output
Pulse A is used as pulse output. Pulse B on/off is used as
reversible control.
Reversible control Dual-pulse output
Pulse A is used as forward pulse (CW) output.Pulse B is
used as reverse pulse (CCW) output.
Command Operating Condition
Output Used
All-in-One CPU Module
CAN J1939 All-in-One CPU
Module/Plus CPU Module
Pulse Output
Reversible
Control Output
Pulse Output
Reversible
Control Output
JOG1
Reversible control disabled Q0 — Q0 —
Reversible control Single-pulse output Q0 Q2
*1
Q0 Q1
Reversible control Dual-pulse output Q0, Q1
*2
—Q0, Q1—
JOG2
Reversible control disabled Q1 — Q2 —
Reversible control Single-pulse output Q1 Q3
*1
Q2 Q3
Reversible control Dual-pulse output ——Q2, Q3—
9.
8.
7.
6.
10.
11.
12.
13.
Q0
Q0
Q2
Q0
Q1

Table of Contents

Other manuals for IDEC MICROSmart FC6A Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the IDEC MICROSmart FC6A Series and is the answer not in the manual?

IDEC MICROSmart FC6A Series Specifications

General IconGeneral
BrandIDEC
ModelMICROSmart FC6A Series
CategoryComputer Hardware
LanguageEnglish

Related product manuals