19: PID C
ONTROL
I
NSTRUCTION
Ladder program
Device Address Comment Device Address Comment
D0000 Process variable (after conversion) M0000 Control action
D0002 Operating status M0003 Alarm 1 output
D0007 Set point M0020 Analog input status error
D8178 Analog Status to the Analog I/O Cartridge M0021 Analog output status error
D8186 Analog Value to the Analog I/O Cartridge M0022 PID error
D8188 Analog Status to the Analog I/O Cartridge M8120 Initialize pulse
I0000 PID control enable input
Q0001 Alarm lamp
1. When I0000 is ON and the analog input status error for the analog I/O cartridge is 5, 6, or 8 to 11, M0020 turns ON.
When the analog output status error for the analog I/O cartridge is 8 to 11, M0021 turns ON.
2. The PID instruction operates when I0000 is ON and both M0020 and M0021 are OFF.
The operating status of the PID instruction is judged, and when an error occurs, M0022 turns ON.
3. When M0020 or M0021 is ON, or when I0000 is OFF (when the PID instruction is stopped), 0 is stored in D8186 and 0 V
is output from AQ4.
4. The operating status of the PID instruction is judged, and when an error occurs, M0021 turns ON.
5.
When either M0020, M0021, M0022, or M0003 (Alarm 1 output (process high alarm)) is ON, Q0001 (alarm lamp) turns ON.
Alarm
lamp
Q0001
PIDA S1
D0000
Process variable
(aft er co nversion)
S2
M8120
S4
D0007
S3
M0000
Initialize pulse Control action Set point
Analog input
status error
M0020
CMP>=(W) S1 -
D8172
S2 -
5
REPD1 -
M0020
Analog Status to
the Analog I/O Cartridge
Analog input
status error
Analog output
status error
M0021
PID error
M0022
Alarm 1 output
M0003
ICMP>=(W) S1
109
S2
D0002
D1
M0022
S3
103
Operating status
Operating status
error
CMP>=(W) S1 -
D8176
S2 -
5
REPD1 -
M0021
Analog Status to
the Analog I/O Cartridge
Analog output
status error
MOV(W) S1 -
0
D1 -
D8174
REP
Analog Value to
the Analog I/O Cartridge
Analog output
status error
M0020
Analog input
status error
M0021
PID control
enable input
I0000
PID control
enable input
I0000
PID control
enable input
I0000
PID control
enable input
I0000
ICMP>=(W) S1
109
S2
D0002
D1
M0021
S3
103
Operating status
Analog output
status error
Analog input
status error
M0020
Analog output
status error
M0021
1.
2.
3.
4.
5.

Table of Contents

Other manuals for IDEC MICROSmart FC6A Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the IDEC MICROSmart FC6A Series and is the answer not in the manual?

IDEC MICROSmart FC6A Series Specifications

General IconGeneral
BrandIDEC
ModelMICROSmart FC6A Series
CategoryComputer Hardware
LanguageEnglish

Related product manuals