SD1 Series Inverters Fault Tracking
-104-
Ensure the contactor is
Visual examination NA
Control
circuit
PCB and plugs
loose screws and
Fasten up NA
Ensure there is no
odors and color
Smelling and visual
examination
NA
cracks, damage,
Visual examination NA
Ensure there is no
weeping and distortion
to the capacitors.
Visual examination
or estimate the
usage time
according to the
maintenance
NA
Cooling
system
Cooling fan
is abnormal noise and
examination or
Stable rotation
Ensure there is no loose
Tighten up NA
Ensure there is no
color-changing caused
by overheating.
or estimate the
usage time
according to the
maintenance
NA
Ventilating duct
Ensure no foreign
objects are in the
cooling fan air vent.
Visual examination NA
6.1.2 Cooling fan
The inverter's cooling fan has a minimum life span of 25,000 operating hours. The actual life
span depends on the inverter usage and ambient temperature.
The operating hours can be found through P07.14 (accumulative hours of the inverter).
Fan failure can be predicted by the increasing noise from the fan bearings. If the inverter is