SD1 Series Inverters Function Parameters
-68-
Function
code
Name Description Default Modify
P06.23
Corresponding
AO2 output to
the lower limit
10V (20mA)
0.0% 100.0%
AO
Setting range of P06.17: -100.0%~ P06.19
Setting range of P06.18: 0.00V~10.00V
Setting range of P06.19: P06.17~100.0%
Setting range of P06.20: 0.00V~10.00V
Setting range of P06.21: 0.000s~10.000s
Setting range of P06.22:- 100.0%~ P06.24
Setting range of P06.23: 0.00V~10.00V
Setting range of P06.24: P06.22~100.0%
Setting range of P06.25: 0.00V~10.00V
Setting range of P06.26: 0.000s~10.000s
0.00V
P06.24
Upper limit of
AO2 output
100.0%
P06.25
Corresponding
AO2 output to
the upper limit
10.00V
P06.26
AO2 output
filter time
0.000s
P07 Group HMI
Function
code
Name Description Default Modify
P07.00 User password
0~65535
The password protection will be valid when
setting any non-zero number.
00000: Clear the previous user's password and
make the password protection invalid.
After the user's password becomes valid, if the
password is incorrect, users cannot enter the
parameter menu. Only correct password can
make the user check or modify the parameters.
Please remember all users' passwords.
Retreat editing state of the function codes and
the password protection will become valid in 1
minute. If the password is available, press
PRG/ESC to enter
the editing state of the
function codes, and then "0.0.0.0.0" will be
displayed. Unless input r
ight password, the
operator cannot enter it.
Note:
Restoring to the default value can clear
the password, please use it with caution.
0