SD1 Series Inverters Communication Protocol
-138-
Function
instruction
Address
definition
Data meaning instruction
R/W
characteristics
0003H: Forward jogging
0004H: Reverse jogging
0005H: Stop
0006H: Coast to stop (emergency stop)
0007H: Fault reset
0008H: Jogging stop
RTU mode:
The command sent by the master:
Parameters
address
CRC check
VFD
address
Write
command
Forward
running
If the operation is successful, the response may be as below (the same with the command
sent by the master):
Parameters
address
CRC check
VFD
address
Write
command
Forward
running
ASCII mode:
The command sent to the inverter:
Parameters
address
VFD
address
Write
command
LRC
check
Data
number
If the operation succeeds, the response message is as follows:
Parameters
address
VFD
address
Write
command
LRC
check
Data
number
Example 2: set the max. output frequency of the inverter with the address of 03H as100Hz.
Function
code
Name Description Default Modify
P00.03
Max. output
frequency
Used to set the max. output frequency of
the
inverter
. It is the basis of frequency
setup and the acceleration/deceleration.
Setting range: P00.04~400.00Hz
50.00Hz
See the figures behind the radix point, the fieldbus ratio value of the max. output frequency
(P00.03) is 100. 100Hz timed by 100 is 10000 and the corresponding hex is 2710H.
RTU mode:
The command sent by the master: