Setting range of P01.09: 0.00Hz–P00.03 (max.
output frequency)
Setting range of P01.10: 0.00–30.00s
Setting range of P01.11: 0.0–100.0% (of the rated
VFD output current)
Setting range of P01.12: 0.0–50.0s
This function code refers to the transition time of
the threshold set by P01.14 during setting
forward/reverse rotation of the VFD, as shown
below.
0: Switch over after zero frequency
1: Switch over after starting frequency
2: Switch over after passing stop speed and delay
When the running command channel is controlled
by terminals, the system will detect running
terminal state automatically during power up.
0: Terminal running command is invalid during
power up. The VFD will not run during power up
even if the running command terminal is detected
to be valid, and the system is in running protection
state. The VFD will run only after this terminal is
cancelled and enabled again.
1: Terminal running command is valid during
power up. The system will start the VFD
automatically after initialization is done if the
running command terminal is detected to be valid
during power up.
Note: This function must be set with caution,
otherwise, serious consequences may occur.