Goodrive350 IP55 High-ingress Protection Series VFD Function parameter list
-146-
Function
code
Name
Description
Default
value
Modify
P04.36
VF pull-in
current
frequency
switch-over
threshold of
synchronous
motor
When the synchronous motor VF control mode
is enabled, this parameter is used to set the
frequency threshold for the switching between
injection current 1 and injection current 2.
Setting range: 0.0%200.0% (of the motor rated
frequency)
20.0%
P04.37
VF reactive
closed-loop
proportional
coefficient of
synchronous
motor
When the synchronous motor VF control mode
is enabled, this parameter is used to set the
proportional coefficient of the reactive current
closed-loop control.
Setting range: 03000
50
P04.38
VF reactive
closed-loop
integral time of
synchronous
motor
When the synchronous motor VF control mode
is enabled, this parameter is used to set the
integral coefficient of the reactive current
closed-loop control.
Setting range: 03000
30
P04.39
VF reactive
closed-loop
output limit of
synchronous
motor
When the synchronous motor VF control mode
is enabled, this parameter is used to set the
output limit of the reactive current in the
closed-loop control. A greater value indicates a
higher reactive closed-loop compensation
voltage and higher output power of the motor. In
general, you do not need to modify this
parameter.
Setting range: 016000
8000
P04.40
Enable/disable
IF mode of
asynchronous
motor 1
0: Disabled
1: Enabled
0
P04.41
IF current setting
of asynchronous
motor 1
When IF control is adopted for asynchronous
motor 1, this parameter is used to set the output
current. The value is a percentage in relative to
the rated current of the motor.
Setting range: 0.0200.0%
120.0%
P04.42
IF proportional
coefficient of
asynchronous
motor 1
When IF control is adopted for asynchronous
motor 1, this parameter is used to set the
proportional coefficient of the output current
closed-loop control.
Setting range: 05000
650
P04.43
IF integral
coefficient of
asynchronous
motor 1
When IF control is adopted for asynchronous
motor 1, this parameter is used to set the
integral coefficient of the output current
closed-loop control.
Setting range: 05000
350