Goodrive350 IP55 High-ingress Protection Series VFD Function parameter list
-177-
negative value means reverse running.
P10.02
P10.04
P10.06
P10.32
P10.30
P10.28
Deceleration time
(two sections)
Acceleration time
(two sections)
P10.03 P10.05 P10.07 P10.31 P10.33
When selecting multi-step speed running, the
multi-step speed is within the range of -fmax–
fmax, and it can be set continuously. The start/stop
of multi-step stop is also determined by P00.01.
The Goodrive350 IP55 high-ingress protection
series VFD can set 16-step speed, which are set
by combined codes of multi-step terminals 1–4
(set by S terminal, correspond to function code
P05.01–P05.06) and correspond to multi-step
speed 0 to multi-step speed 15.
Output frequency
t
t
t
t
t
terminal 1
terminal 2
terminal 3
terminal 4
0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
ON ON
ON
ON ON
ON ON ON
ON
ON
ON
ON
ON
ON
ON
When terminal 1, terminal 2, terminal 3 and
terminal 4 are OFF, the frequency input mode is
set by P00.06 or P00.07. When terminal 1,
terminal 2, terminal 3 and terminal 4 are not all
OFF, the frequency set by multi-step speed will
prevail, and the priority of multi-step setting is
higher than that of the keypad, analog, high-speed
pulse, PID, and communication settings.
The relation between terminal 1 (T1), terminal 2
(T2), terminal 3 (T3) and terminal 4 (T4) are shown
in the table below.