Goodrive350 IP55 High-ingress Protection Series VFD Function parameter list
-181-
Function
code
Name
Description
Default
value
Modify
alarm, and stops running after overload fault.
2: The VFD continues running after overload
alarm, and stops running after underload fault.
3: The VFD stops running after overload/underload
fault.
Hundreds place:
0: Always detect
1: Detect during constant-speed running
Thousands place: VFD overload current reference
selection
0: Related to current calibration coefficient
1: Irrelated to current calibration coefficient
P11.09
Overload
pre-alarm
detection level
If the VFD or motor output current is larger than
the overload pre-alarm detection level (P11.09),
and the duration exceeds the overload pre-alarm
detection time (P11.10), overload pre-alarm signal
will be outputted.
Y,
RO1, RO2
Output current
Overload pre-alarm
threshold
Time t
Time t
Pre-alarm time tPre-alarm time t
Setting range of P11.09: P11.11200% (relative
value determined by the ones place of P11.08)
Setting range of P11.10: 0.13600.0s
G model:
150%
P model:
120%
P11.10
Overload
pre-alarm
detection time
1.0s
P11.11
Underload
pre-alarm
detection level
Underload pre-alarm signal will be outputted if the
output current of the VFD or motor is lower than
underload pre-alarm detection level (P11.11), and
the duration exceeds underload pre-alarm
detection time (P11.12).
Setting range of P11.11: 0 P11.09 (relative value
determined by the ones place of P11.08)
Setting range of P11.12: 0.13600.0s
50%
P11.12
Underload
pre-alarm
detection time
1.0s
P11.13
Fault output
terminal action
during fault
This function code is used to set the action of fault
output terminals during undervoltage and fault
reset.
0x000x11
Ones:
0x00