Goodrive350 IP55 High-ingress Protection Series VFD Basic Operation Instructions
-52-
Function
code
Name
Description
Default
value
P03.20
Set upper limit of the torque
when motoring via keypad
0.0300.0% (rated motor current)
180.0%
P03.21
Set upper limit of brake
torque via keypad
180.0%
P03.22
Flux-weakening coefficient
in constant power area
0.12.0
0.3
P03.23
Min. flux-weakening point
in constant power area
10%100%
20%
P03.24
Max. voltage limit
0.0120.0%
100.0%
P03.25
Pre-exciting time
0.00010.000s
0.300s
P03.32
Torque control enable
0:Disable
1:Enable
0
P03.33
Flux weakening integral
gain
08000
1200
P03.35
Control optimization setting
00x1111
Ones place: Torque command selection
0: Torque reference
1: Torque current reference
Tens place: Reserved
0: Reserved
1: Reserved
Hundreds place: Whether to enable ASR
integral separation
0: Disable
1: Enable
Thousands place: Reserved
0: Reserved
1: Reserved
0x0000
P03.36
ASR differential gain
0.0010.00s
0.00s
P03.37
High-frequency ACR
proportional coefficient
In the closed-loop vector control mode
(P00.00=3), when the frequency is lower
than the ACR high-frequency switching
threshold (P03.39), the ACR PI parameters
are P03.09 and P03.10; and when the
frequency is higher than the ACR
high-frequency switching threshold (P03.39),
the ACR PI parameters are P03.37 and
P03.38.
Setting range of P03.37: 065535
Setting range of P03.38: 065535
Setting range of P03.39: 0.0100.0% (in
relative to the maximum frequency)
1000
P03.38
High-frequency ACR
integral coefficient
1000
P03.39
ACR high-frequency
switching threshold
100.0%
P17.32
Flux linkage
0.0200.0%
0.0%