Goodrive350 IP55 High-ingress Protection Series VFD Basic Operation Instructions
-72-
Function
code
Name
Description
Default
value
P01.10
Waiting time of DC brake
after stop
0.0050.00s
0.00s
P01.11
DC brake current of stop
0.0100.0%
0.0%
P01.12
DC brake time of stop
0.0050.00s
0.00s
P01.13
Deadzone time of
forward/reverse rotation
0.03600.0s
0.0s
P01.14
Forward/reverse rotation
switch-over mode
0: switch over after zero frequency
1: switch over after starting frequency
2: switch over after passing stop speed
and delay
1
P01.15
Stop speed
0.00100.00Hz
0.50 Hz
P01.16
Stop speed detection mode
0: Set value of speed (the only detection
mode valid in SVPWM mode)
1: Detection value of speed
1
P01.18
Power-on terminal running
protection selection
0: Terminal running command is invalid at
power up
1: Terminal running command is valid at
power up
0
P01.19
Action selection when the
running frequency is below
lower limit (lower limit should
be larger than 0)
Ones place: Action selection
0: Run at the lower limit frequency
1: Stop
2: Sleep
Tens place: Stop mode
0: Coast to stop
1: Decelerate to stop
0
P01.20
Wake-up-from-sleep delay
0.03600.0s (valid when the ones place of
P01.19 is 2)
0.0s
P01.21
Restart after power cut
0: Restart is disabled
1: Restart is enabled
0
P01.22
Waiting time of restart after
power cut
0.03600.0s (valid when P01.21 is 1)
1.0s
P01.23
Start delay
0.060.0s
0.0s
P01.24
Stop speed delay
0.0100.0s
0.0s
P01.25
Open-loop 0Hz output
selection
0: No voltage output
1: With voltage output
2: Output as per DC brake current of stop
0
P01.26
Deceleration time of
emergency-stop
0.060.0s
2.0s
P01.27
Time of starting section of
deceleration S curve
0.050.0s
0.1s