JOHNSON CONTROLS
128
FORM 145.05-NOM7
ISSUE DATE: 10/31/2019
SECTION 5 – SEQUENCE OF OPERATION
Required Program Values
• PROGRAM key, ECONOMIZER subsection:
ā€œFLUSH CYCLEā€ must be set to ENABLE
• SETPOINTS key, ECONOMIZER subsec-
tion: ā€œFLUSH DELAY TIMEā€ must be set for
the amount of delay from the time the ā€œFLUSH
CYCLEā€ is activated until the sequence begins
(default is 0 minutes)
• OPTIONS key, ECONOMIZER subsection:
ā€œECONOMIZER INSTALLEDā€ must be set to
WATERSIDE
Sequence of Operation - Scheduled On/
Off Operation
The following criteria must be met before the control-
ler initiates a Flush Cycle:
• ā€œFLUSH CYCLEā€ is ENABLED
• ā€œECONOMIZER INSTALLEDā€ is set to WA-
TERSIDE
The following must have happened or is in present
state:
• Time is between 7:00 PM and 11:59 PM (19:00
and 23:59); this is usually because these are the
most common times when units are UNOCCU-
PIED,
And
• Unit is in an UNOCCUPIED mode of operation,
And
• No compressors have been ON in the past 5 min-
utes,
And
• 18 hours has elapsed since the last Flush Cycle
Upon initiation of the Flush Cycle, the controller com-
pletes the following:
• Starts a countdown timer to countdown the
time indicated by the ā€œFLUSH DELAY TIMEā€
setpoint. Wait until the timer expires.
• Turns the ā€œPUMP STARTā€ BO to ON
• Changes the ā€œCURRENT OPER MODEā€ to
ā€œFLUSHING ECONO COILā€
• Drives the ā€œCOND WATER VALVEā€ to 0% (10
VOLTS)
• Drives the ā€œECONOMIZER WATER VALVEā€ to
100% (10 VOLTS)
• Waits 3 minutes
• Drives the ā€œCOND WATER VALVEā€ to "COND
VALVE MIN POS"
• Drives the ā€œECONOMIZER WATER VALVEā€ to
ā€œWATER ECONO MIN POSITIONā€
• Waits 1 minute
• Turns the ā€œPUMP STARTā€ DO to OFF
Changes ā€œCURRENT OPER MODEā€ back to previous
mode and resume normal operation.
Sequence of Operation - Scheduled 24/7
Operation
The following criteria must be met before the control-
ler initiates a Flush Cycle:
• ā€œFLUSH CYCLEā€ is ENABLED
• ā€œECONOMIZER INSTALLEDā€ is set to WA-
TERSIDE
• Time is 11:59 PM (23:59),
And
No compressors have been ON for the past 5 min-
utes,
And
18 hours has elapsed since the last Flush Cycle
Upon initiation of the Flush Cycle, the controller com-
pletes the following:
• Turn the ā€œPUMP STARTā€ BO to ON
• Change the ā€œCURRENT OPER MODEā€ to
ā€œFLUSHING ECONO COIL
• Drive the ā€œCOND WATER VALVEā€ to 0% (10
VOLTS)
• Drive the ā€œECONOMIZER WATER VALVEā€ to
100% (10 VOLTS)
• Wait 3 minutes
• Drive the ā€œCOND WATER VALVEā€ to ā€œCOND
VALVE MIN POSā€
• Drive the ā€œECONOMIZER WATER VALVEā€ to
ā€œWATER ECONO MIN POSITIONā€

Table of Contents

Other manuals for Johnson Controls LSWU035

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Johnson Controls LSWU035 and is the answer not in the manual?

Johnson Controls LSWU035 Specifications

General IconGeneral
BrandJohnson Controls
ModelLSWU035
CategoryChiller
LanguageEnglish

Related product manuals