SECTION 6 – USER INTERFACE CONTROL CENTER
DISPLAY TEXT TYPE ID VALUE RANGE LOCATION DESCRIPTION
Outside Air
Temp
Analog
Input
J9-6 0-5 Volts I/O Board
Analog Input from the Outdoor Air
Temperature Sensor
Piezometer
Pressure
Analog
Input
0-5 Volts Tb1-20
The Piezometer measures the
amount of CFMs the fan is producing
Pressure
Discharge A
Analog
Input
J6-1 0-5 Volts I/O Board
Analog Input from the System A Dis-
charge Pressure Transducer
Pressure
Discharge B
Analog
Input
J6-3 0-5 Volts I/O Board
Analog Input from the System B Dis-
charge Pressure Transducer
Pressure
Discharge C
Analog
Input
J7-1 0-5 Volts I/O Board
Analog Input from the System C Dis-
charge Pressure Transducer
Pressure
Discharge D
Analog
Input
J7-3 0-5 Volts I/O Board
Analog Input from the System D Dis-
charge Pressure Transducer
Pressure
Discharge E
Analog
Input
J8-1 0-5 Volts I/O Board
Analog Input from the System E Dis-
charge Pressure Transducer
Pressure
Dis-
charge F
Analog
Input
J8-3 0-5 Volts I/O Board
Analog Input from the System F Dis-
charge Pressure Transducer
Pressure
Suction A
Analog
Input
J6-2 0-5 Volts I/O Board
Analog Input from the System A Suc-
tion Pressure Transducer
Pressure
Suction B
Analog
Input
J6-4 0-5 Volts I/O Board
Analog Input from the System B Suc-
tion Pressure Transducer
Pressure
Suction C
Analog
Input
J7-2 0-5 Volts I/O Board
Analog Input from the System C Suc-
tion Pressure Transducer
Pressure Suc-
tion D
Analog
Input
J7-4 0-5 Volts I/O Board
Analog Input from the System D Suc-
tion Pressure Transducer
Pressure
Suction E
Analog
Input
J8-2 0-5 Volts I/O Board
Analog Input from the System E Suc-
tion Pressure Transducer
Pressure
Suction F
Analog
Input
J8-4 0-5 Volts I/O Board
Analog Input from the System F Suc-
tion Pressure Transducer
Return Air
Humidity
Analog
Input
J11-5 0-5 Volts I/O Board
Analog Input from the Return Air
Humidity Sensor
Return Air
Temp Current
Analog
Input
J9-4 0-5 Volts I/O Board
Analog Input from the Return Air
Temperature Sensor
Supply Air
Temp Current
Analog
Input
J9-2 0-5 Volts I/O Board
Analog Input from the Supply or
Mixed Air Sensor
Underfloor Air
Humidity
Analog
Input
J11-8 0-5 Volts I/O Board
Analog Input from the Underoor
Humidity Sensor
Underfloor
Slab Temp
Analog
Input
Tb1-16 0-5 Volts I/O Board
Analog Input from the Under Floor
Temperature Sensor
Vent Override
Analog
Input
Tb1-18 0-5 Volts I/O Board
Analog Input to Control the Econo-
mizer Damper
Water Temper-
ature Entering
Analog
Input
J9-12 0-5 Volts I/O Board
Analog Input from the Entering Cond
Water Temp Sensor
Water Temper-
ature Leaving
Analog
Input
J9-14 0-5 Volts I/O Board
Analog Input from the Leaving Cond
Water Temp Sensor
Zone Temp
Current
Analog
Input
Tb1-14 0-5 Volts I/O Board
Analog Input from the Zone Tempera-
ture Sensor
Bypass Damp-
er Position
Analog
Output
J15-11 0-10 VDC I/O Board
Analog Output to the FlexSys Bypass
Damper
Cond Water
Valve
Analog
Output
J15-8 2-10 VDC I/O Board
Analog Output to the Condenser
Water Valve
TABLE 40 - SERVICE (CONT'D)