ter 8 DETAIL PERFORMANCE SETTINGS
1
2
8.11.1 SCANNER
Alarm Detection On: An abnormal condition is detected and an alarm is generated.
Off: An alarm does not occur.
“Detection Time” the time from when an abnormality is detected until an alarm occurs.
You can set between 0 and 999 seconds.
If a normal condition is detected within a set time after an error is detected, no alarm is generated.
Note
The communication cycle for reporting the status varies depending on the device.
If a detection time shorter than the communication cycle is set, an abnormal condition may be
recognized incorrectly.
8.11.2 DISPLAY UNIT
Set alarm detection for the Display Unit.
The contents that can be set by selecting each item and the operation method are the same as for
8.11.1 SCANNER.
Select each setting item㻌
㻌
Select an item and change the setting.㻌
*The setting items that are displayed are the same even if you
select something other than “Scanner(Time Out)”.