CHAPTER 18
Power and Electrical Safety Information
General Electrical Safety Guidelines and Warnings on page 179
Prevention of Electrostatic Discharge Damage on page 180
AC Power Electrical Safety Guidelines on page 182
AC Power Disconnection Warning on page 183
DC Power Electrical Safety Guidelines on page 184
DC Power Disconnection Warning on page 186
DC Power Grounding Requirements and Warning on page 188
DC Power Wiring Sequence Warning on page 189
DC Power Wiring Terminations Warning on page 190
TN Power Warning on page 192
Action to Take After an Electrical Accident on page 192
General Electrical Safety Guidelines and Warnings
This topic applies to hardware devices in the EX Series product family, which includes
switches and the XRE200 External Routing Engine.
This topic also applies to hardware devices in the QFX Series.
WARNING: Certain ports on the device are designed for use as intrabuilding
(within-the-building) interfaces only (Type 2 or Type 4 ports as described in
GR-1089-CORE,Issue4) and require isolation from the exposedoutside plant
(OSP) cabling. To comply with NEBS requirements and protect against
lightning surges and commercial power disturbances, the intrabuilding ports
must not be metallically connected to interfaces that connect to the OSP or
its wiring. The intrabuilding ports on the device are suitable for connection
to intrabuilding or unexposed wiring or cabling only. The addition of primary
protectors is not sufficient protection for connecting these interfaces
metallically to OSP wiring.