Docu-No.: 0590020601-EN Rev. 1.6.0 Page 103
Appendix 5
Service variables 5.6
PertValueMode 0 = PertValue is displayed in Grams
1 (default) = PertValue is displayed as a % of setpoint. With setpoint=0,
pertvalue is shown in Grams.
MFDispFilter2 For LWF Only: If <0>, the massflow display is filtered only by the variable
<MF Display Filter>. If <1>, the display is filtered by 1 times more. If <2>,
the display is filtered by two times more. etc. Maximum value = 100.
VolRate If set to other than <0>, this will add a variable <BULK DENSITY> to the
<PRODUCT CHANGE> menu. After a Auto FF calibration is done, this
value will display the volumetric capacity of the feeder.
ForceVibAlgo This allows to interface the AC board to 3rd party vibratory drive. If set to
<1> that is used to unhide the menu parameters for the tuning and calib.
ScaleRange Input from the scale range.
RefillRepTm This parameter is zero by default. When 0, the refilling functions are all
the same as before. To enable this feature, (auto restart) this new
parameter must be set to a non-zero value, such as 60 (seconds) and
the refill must be programmed to Auto Terminate. Then, when there is a
refill time out and the Net Weight is still below the refill request point, the
refill terminates (as normal), but also will start the AutoTerm Refill
Repeat Timer. When this AutoTerm Refill Repeat Timer expires, the refill
cycle starts over again automatically. This continues until the weight
goes at least above the refill request point.
Desc
Variable
Current Value
Table page 2 of 2