EasyManua.ls Logo

K-TRON K-Vision - Modbus I-O Sub-Menu

K-TRON K-Vision
121 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Docu-No.: 0590020601-EN Rev. 1.6.0 Page 53
Programming Reference 1
I/O Menu 1.8
1.8.5 Modbus I-O sub-menu
Note:
This menu is not available on the KSL, K-Vision or KSC.
Parameter
Definition
ADDR 80 - 83
These are the read only I-O addresses for any external Modbus I-O
that has been connected to K-Port 2. For each address, the module
type (if connected) or problem will be indicated. Possibilities at each
address are: WAGO, MISSING, CONFLICT, NONE
WAGO = the Wago system of Modbus I-O modules is connected.
CONFLICT = Addresses of connected modules are in conflict after
powering the system. Select <REBIND NOW>. Press ENT twice to
clear the fault.
MISSING or CHANGED = Module that was present is no longer
found. Select <REBIND NOW>. Press ENT twice to clear the fault.
Input range: 80 to 83 Default: 80
DETAILS
This read only parameter presents information about the operation
of each connected external Modbus I-O device.
Node Select: 80, 81, 82, 83
Type Select: Anlg In, Anlg Out, Dig In, and Dig Out are the possible
functionality for connected modules
I/O Point: 1-8.
Up to 8 points, of the same type, are possible at any address.
REBIND NOW
When the I-O functions have been configured, press the ENT key
twice to rebind variables to the I-O points installed.
Note:
If alarm 39 occurs (Ext_IO_Fail), the Rebind Now function can clear
the alarm. However, this action will remove all external I-O function.
It is best to examine why the external module failed before executing
Rebind Now.
The Rebind Now function assigns <None> to any previously
programmed external I-O point and then performs a new binding
based upon the rule as follows:
Lowest module by address with lowest I-O point is assigned the
lowest I-O number
e.g. Four digital input module at address 80 is automatically bound
with EXTIN1 at module input 0 to EXTIN 4 at module input 3.
After the Rebind Now action, each I-O point requires reassignment
of its function. e.g. <Start>.

Table of Contents

Related product manuals