Page 8.1 - 6 COMBIVERT F5-A, -E, -H © KEB, 2012-10
Troubleshooting
Display COMBIVIS Value Meaning
E.LSF
Error ! load shunt fault 15
Error: Load-shunt relay has not picked up, occurs for a short
time during the switch-on phase, but must automatically be reset
immediately. If the error message remains the following causes may
be applicable:
load-shunt defective
input voltage wrong or too low
high losses in the supply cable
braking resistor wrongly connected or damaged
braking module defective
E.ndOH no ERROR drive overheat 11
Motor temperature switch or PTC at the terminals T1/T2 is again in
the normal operating range. The error can be reset now.
E.nOH no E. over heat pow.mod. 36
Temperature of the heat sink is again in the permissible operating
range. The error can be reset now.
E.nOHI no ERROR overheat int. 7
No longer overheating in the interior E.OHI, interior temperature has
fallen by at least 3°C
E.nOL no ERROR overload 17
No more overload, OL-counter has reached 0%; after the error E.OL a
cooling phase must elapse. This message appears upon completion
of the cooling phase. The error can be reset now. The inverter must
remain switched on during the cooling phase.
E.nOL2 no ERROR overload 2 20 The cooling time has elapsed. The error can be reset.
E.OC
Error ! overcurrent 4
Occurs, if the specied peak current is exceeded. Causes:
acceleration ramps too short
the load is too big at switched off acceleration stop and switched off
constant current limit
short-circuit at the output
ground fault
deceleration ramp too short
motor cable too long
EMC
DC brake at high ratings active (see 7.15.5)
E.OF ERROR! overfrequency 61 Current frequency is above the permissible range.
E.OH
Error ! overheat pow.mod. 8
Overtemperature of power module. Error can only be reset at E.nOH.
Causes:
insufcient air ow at the heat sink (soiled)
ambient temperature too high
ventilator clogged
E.OH2
Error ! motor protection 30 Electronic motor protective relay has tripped.
E.OHI
Error ! overheat internal 6
Overheating in the interior: error can only be reset at E.nOHI, if the
interior temperature has dropped by at least 3 °C.
E.OL
Error ! overload (Ixt) 16
Overload error can only be reset at E.nOL, if OL-counter reaches 0%
again. Occurs, if the overload is longer than the permissible time (see
technical data). Causes:
poor controller adjustment
mechanical fault or overload in the application
inverter not correctly dimensioned
motor wrongly wired
encoder defective
further on next side

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the KEB COMBIVERT F5-A and is the answer not in the manual?

KEB COMBIVERT F5-A Specifications

General IconGeneral
BrandKEB
ModelCOMBIVERT F5-A
CategoryControl Unit
LanguageEnglish

Related product manuals