Page 6.2 - 12 COMBIVERT F5-A, -E, -H © KEB, 2012-10
Start-up
2. Selection of the speed range
The required speed range (e.g.: 0..+/- 4000 rpm) is selected
in control type Ud.02.
⇒ Ud.02 control type = 4…7
The speed range should be selected at least 10% higher
than the highest setpoint speed in the application.
Attention: Changing the control type
releases loading of the default para-
meters!
All data for the adjustment of the con-
trol type (e.g. resolution of the speed,
etc.) see chapter 5.1.
3. Loading the default parameters
If the control type Ud.02 was not changed, loading of the
default parameters (KEB factory setting) can be released by
⇒ Fr.01 copy parameter set = - 4
can be triggered
Attention: Pre-adjustments (e.g. func-
tion of the digital inputs) disappear
4.
Selectionofthecontrollerconguration
adjust speed-controlled operation
⇒ cS.00 speed control cong. = 4
(control mode = speed control)
5. Select source of the speed feedback
Motor speed feedback not available.
⇒ cS.01 actual source = 2: calculated actual value