EasyManua.ls Logo

Lenze i700

Lenze i700
359 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
7 CiA402 device profile
7.10 Cyclic sync torque mode (cst)
235
Lenze · i700 servo inverter · reference manual · DMS 3.0 EN · 06/2016 · TD06
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
0x6073 | 0x6873 - Max current
Tip!
More torque characteristics can be found on the Internet:
Maximum current (maximum overload current of the device)
•100% rated motor current (0x6075
or 0x6875 for axis B)
This parameter serves to limit the inverter output current.
The value to be set here results from the maximum torque required for the process and the connected motor.
The value is calculated according to the following rule of thumb:
For synchronous motors (SM):
Axis A: 0x6073 [%] = M
max_process
[Nm] / 0x6076 [Nm] * 100
Axis B: 0x6873 [%] = M
max_process
[Nm] / 0x6876 [Nm] * 100
For asynchronous motors (ASM):
Axis A: 0x6073 [%] = M
max_process
[Nm] / 0x6076 [Nm] * 115
Axis B: 0x6873 [%] = M
max_process
[Nm] / 0x6876 [Nm] * 115
For both motor types:
Axis A: 0x6072
[%] = M
max_process
[Nm] / 0x6076 [Nm] * 100
Axis B: 0x6872
[%] = M
max_process
[Nm] / 0x6876 [Nm] * 100
Depending on the motor frame size, the Lenze setting of 0x6073 (or 0x6873 for axis B) and 0x6072
(or 0x6872
for axis B) serves to achieve a rated current of 150 % in case of synchronous motors and a rated current of 130 %
in case of asynchronous motors. If the process (application) needs torques above these limits, these two
parameters have to be set accordingly based on the motor data.
If a value is set here which, multiplied by the rated motor current (0x6075
or 0x6875 for axis B) leads to a higher
current value than the maximum device current, the value is limited device-internally to a maximum device
current / rated motor current of 100 % * and output as warning in the logbook. The value set here, however, is
not changed.
Note!
This parameter is not identical to the ultimate motor current I
ULT
(0x2D46:1 or 0x3546:1 for axis B!
The ultimate motor current is a limit value for synchronous motors in order to protect their magnets.
The value to be set here should always be considerably below the ultimate motor current!
Setting range (min. value | unit | max. value) Lenze setting
0.0 % 3276.7 150.0 %
Write access CINH OSC P RX TX Scaling: 1/10 UNSIGNED_16
Example calculation based on the torque characteristics for MCS06C41 Lenze motor
The data apply to a mains voltage 3 x 400 V
M
max_process
0x6073 = M
max_process
/ M
rated_motor
* 100 % = 1.5 Nm / 0.7 Nm * 100 % = 215 %
M
rated_motor

Table of Contents

Other manuals for Lenze i700

Related product manuals