9 Diagnostics & error management
9.4 CiA402 error codes / error messages
295
Lenze · i700 servo inverter · reference manual · DMS 3.0 EN · 06/2016 · TD06
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
Error code 0xFF09: Motor phase failure
Text ID: 0x27
Motor phase failure monitoring
Error code 0xFF0A: Motor phase failure - phase U
Text ID: 0x28
Motor phase failure monitoring
Error code 0xFF0B: Motor phase failure - phase V
Text ID: 0x29
Motor phase failure monitoring
Error code 0xFF0C: Motor phase failure - phase W
Text ID: 0x2A
Motor phase failure monitoring
Cause Remedies Response
Multiple motor phases are not
connected.
Correct the wiring between the
servo inverter and the motor.
In the case of a false alarm,
increase the threshold values for
monitoring in 0x2D45
| 0x3545.
Default setting: No response
Monitoring takes place before and
during operation. Both monitoring
modes can trigger an error. For
parameter setting of the two
monitoring modes, see
0x2D45
| 0x3545.
Cause Remedies Response
Motor phase U is not connected. Correct the wiring between the
servo inverter and the motor.
In the case of a false alarm,
increase the threshold values for
monitoring in 0x2D45
| 0x3545.
Default setting: No response
Monitoring takes place before and
during operation. Both monitoring
modes can trigger an error. For
parameter setting of the two
monitoring modes, see
0x2D45
| 0x3545.
Cause Remedies Response
Motor phase V is not connected. Correct the wiring between the
servo inverter and the motor.
In the case of a false alarm,
increase the threshold values for
monitoring in 0x2D45
| 0x3545.
Default setting: No response
Monitoring takes place before and
during operation. Both monitoring
modes can trigger an error. For
parameter setting of the two
monitoring modes, see
0x2D45
| 0x3545.
Cause Remedies Response
Motor phase W is not connected. Correct the wiring between the
servo inverter and the motor.
In the case of a false alarm,
increase the threshold values for
monitoring in 0x2D45
| 0x3545.
Default setting: No response
Monitoring takes place before and
during operation. Both monitoring
modes can trigger an error. For
parameter setting of the two
monitoring modes, see
0x2D45
| 0x3545.