Technical data
Leuze electronic RSL 430 106
Tab.15.8: Inputs
Reset +24V, dynamically monitored (0.12s to 4s)
Field pair changeover Selection of 10 or 10+10 field pairs via 10control
cables
+24V, dynamically monitored
Signal definition:
High/logical 1 16-30V
Low/logical 0 <3V
Tab.15.9: Safety-related switching outputs
OSSD transistor safety-related switching outputs 4 safe PNP semiconductor outputs
Short-circuit proof, cross circuit monitored
Minimum Typical Maximum
Response time 80ms
(2 scans)
1000ms
(25 scans)
Switching voltage high active U
B
– 3.2V
Switching voltage low 2.0V
Switching current 300mA
Cut-off frequency f
g
1kHz
Load capacity C
load
100nF
Cable length between safety sensor and load see chapter 8.3 "Connection unit CU429"
Cable resistance 15Ω
Test pulse width 60µs 110µs
Test pulse distance 35ms 40ms 40ms
NOTICE
The safety-related transistor outputs perform the spark extinction. With transistor outputs, it is
therefore neither necessary nor permitted to use the spark extinction circuits recommended by
contactor or valve manufacturers (RC elements, varistors or recovery diodes), since these con-
siderably extend the decay times of inductive switching elements.