Maintenance98
Updating DSP Firmware via CLI
Only update the DSP firmware while the UPS is in Stand-by mode. The REPO terminal of the UPS must
be un-plugged. Do not update firmware while the UPS is on Battery mode.
1. Disconnect the REPO terminal from the rear panel of the UPS, see Figure 5-10 below.
Figure 5-10 REPO Terminal
2. Connect the RJ-45 connector to the RS232 port on UPS. For the connection location, refer to the
appropriate rear-panel description for your UPS model in 1.Rear Panels on page 5.
3. Connect the DB9 connector to a computer with the serial-terminal emulator installed.
4. Open the serial-terminal emulator, and adjust the settings to communicate with the UPS:
Select “Serial” connection for the session.
Check the computer “device management” settings for the communication port (for example COM6),and
select the same port in the emulator.
Select 115200 for the connection speed.
Open the emulator session.
5. On the CLI, enter the username and password:
Default username = user
Default password = 123456
6. On the command line, enter update, then press d on the keyboard, see Figure 5-11 on the next page
7. In the menu bar, select Files Transfer > Ymodem, select the DSP upgrade le, then click Send.