EasyManua.ls Logo

LSIS XBL-C41A

LSIS XBL-C41A
194 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Chapter 10 Example Program
10-15
10.3.2 Setting of Modbus RTU client
Standard settings are as follows to act XBL-C41A of client as Modbus RTU client.
Sequence
Procedure
Setting method
1
Connection
setting
1. Select [Online]-[Connection settings] or click icon ( ).
2. After setting the connection option according to user, click the ‘connection’.
2
Reading IO
information
Select [Online]-[Read IO Information] and
click icon
( ).
IO information of currently mounted is shown on the project window.
3
Standard
settings
1. Select XBL-C41A and write standard settings to be same with [Table 10.3.1] at channel
2. Since station setting doesn’t have meaning when acting as client, set as temporary
station number (0~255).
3. When acting as client mode, active mode should be Use P2P settings.

Table of Contents

Related product manuals