EasyManuals Logo

LSIS XBL-C41A User Manual

LSIS XBL-C41A
194 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #40 background imageLoading...
Page #40 background image
Chapter 4 Basic Setting
4-6
[Figure 4.3.1] Built-in communication standard setting screen
4.3.1 Setting item
When setting Cnet communication parameter, the fact the user should define is as follows [Table 4.3.1]
Item Setting content
Station no.
You can set from station 0 to station 255.
Communicati
on speed
1200, 2400, 4800, 9600, 19200, 38400, 57600,115200 bps available
Data bit
7 or 8 bit available
Parity bit
None, Even, Odd available
Stop bit
1 or 2 bit available
Communicati
on channel
It is fixed as follows according to Cnet type
1) Built-in communication channel 1 : RS-232C , channel 2 : RS-485
2) XBL-C41A channel 1 : not used, channel 2: RS-422/RS-485
3) XBL-C21A channel 1 : not used, channel 2: RS-232C
Delay time
It sets interval of communication frame
Time out
It sets the time waiting respond after requesting data.(100 unit 1~ 65535 available)
[Table 4.3.1] communication parameter setting item

Table of Contents